The Hygrostat is designed to control the relative air humidity inside of enclosures. When connected to an enclosure heater, (de-humidifier), it will turn the heater on at the set humidity level in order to raise the dew point. This helps prevent damage and malfunction of electronic components caused by condensation and corrosion.
Technical Data | |
---|---|
Features | |
Relative Humidity setting rang | RH% 10-90 |
Relative Humidity Hysteresis | RH% 5 (max 10) |
Precision | RH% ±5 |
Max. switching current | NC at 240Vac resistive load A 2.2 |
NC at 120Vac resistive load | A 4.4 |
NO at 240Vac resistive load | A 5 |
NO at 120Vac resistive load | A 10 |
Electrical connections | - 3-pole terminal for 2.5 mm² wire |
Contact type | - Change over |
Protection degree EN60529 | - IP20 |
Operating temperature | °C (°F) -10/+50 (+50/+122) |
Storage temperature | °C(°F) -45/+80 (-49/+176) |